Tech cleaned the leak area on the copper line where the leak was at and brazed it, replaced the bi-flow filter dryer while flowing nitrogen, pressure tested the system and held pressure for 10 minutes, tech evacuated the system below 500 microns. Factory charged the system with R410a refrigerant and tested the system afterwards. System was tested in heat mode and cool mode, operated both sides for 15 minutes. Delta T within specs.