{2003 Goodman/Trane Split System - Suite C} — Tenant informed tech that the system is not operating correctly in cool mode - natural gas heat is operating normally. — Tech noted 24v communicated from thermostat to contactor, with condenser fan running but no compressor operation. — System is void of R-22 refrigerant (109 OZ factory charge), opening the low pressure switch, prohibiting the compressor from running. — Built estimates for leak search with nitrogen and recharging the system with refrigerant. Recommended not recharging refrigerant under current condition without locating the leak and repairing it. Advised tenant that the price to repair will fluctuate depending on the component(s) in need of repair. — Recommended replacing the full system on account of equipment age, condition, and costly repairs with refrigerant that is no longer manufactured and in limited supply. — Tenant will consult landlord for resolution and contact office with conclusion. Collected service call