Tech recovered refrigerant charge and flowed nitrogen while replacing faulty reversing valve and biflow filter drier. System passed positive pressure test at 250 psi and standing vacuum test at 280 microns. Tech recharged system with 9 lbs of new R410a and tested system in each mode. Added 12 additional oz lineset charge to achieve 12 degrees design subcooling. Put warranty sticker on failed part. No charge/install warranty.