— Performed CMA Inspection on 4 Rooftop Gas Package Systems. Cleaned and flushed drain pans & lines, tested electrical and temperatures, changed air filters. — RTU-1 2016 Carrier Gas Package System: Far Back: No challenges or recommendations. — RTU-2 2016 Carrier Gas Package System: Middle Back: Thermostat was found to be inoperable at last maintenance . Thermostat was recommended for replacement. Provided updated estimate for programmable and non programmable thermostat. System non operational until thermostat is replaced. — RTU-3 2016 Carrier Gas Package System: Middle Front: No challenges or recommendations. — RTU-4 2016 Carrier Gas Package System: Far Front: Both sides of dual outdoor fan capacitor tested at or below tolerance. Recommend replacing with 2 10 mfd capacitors. Operating outdoor fan motors with weak capacitors will have a negative impact on the efficiency and lifespan of the motors. Provided estimate. — Systems operating with exceptions as noted abov