Tech found head pressure extremely high. Tech found installation manual shredded and imbedded in blower wheel. Bypass damper is set very low. Main downstairs zone damper is stuck closed. Tech removed shredded manual from blower wheel. Turned up static pressure bypass damper and removed failed zone damper motor so downstairs zone is forced open. Customer will talk to the builder about damper. Customer declined maintenance.