TECH PERFORMED CMA INSPECTION ON 1 SPLIT SYSTEM AND 1 GAS FURNACE. SPLIT SYSTEM HAS A PROPER DELTA T READING, SYSTEM IS COOLING PROPERLY. SPLIT SYSTEM FAN CAPACITOR #1 RATED FOR 10mf TESTED WEAK AT 8.89 mf. CAPACITOR DUE FOR FAILURE. RECOMMEND REPLACEMENT OF CAPACITOR. WITH A MEMBER SAVINGS OF $36.70 REPLACEMENT OF THE #1 CAPACITOR WOULD BE $222.00. SPLIT SYSTEM FAN CAPACITOR #2 RATED FOR 10mf TESTED WEAK AT 8.77mf. CAPACITOR DUE FOR FAILURE, RECOMMEND REPLACEMENT OF CAPACITOR. WITH A MEMBER SAVINGS OF $36.70 REPLACEMENT OF 10mf CAPACITOR #2 WOULD BE $222.00. TECH WAS GIVEN APPROVAL TO REPLACE CAPACITORS #1 AND #2 BY MR. SAM. TECH COMPLETED REPLACEMENT OF 2 10mf CAPACITORS FOR SPLIT SYSTEM CONDENSER UNIT. TECH COMPLETED FILTER CHANGE OF 4-16x25x2 FILTERS AND 1-20x25x2 FILTER. THERE ARE PICTURES AND A PERFORMANCE REPORT ATTACHED TO THIS INVOICE. SPLIT SYSTEM FAN CAPACITOR #2 RATED FOR 10mf TESTED WEAK AT 8.77mf. CAPACITOR DUE FOR FAILURE, RECOMMEND REPLACEMENT OF CAPACITOR. SPLIT SYS