Caleb Smith is tentatively available tomorrow. Tech let customer know. System is a 13 year old Carrier 3 ton split heat pump zoned upstairs and downstairs. Tech arrived and confirmed compressor diagnosis from other company was accurate. Compressor is shorted to ground. Tech also found 45/5uf dual run capacitor is reading 11% weak on FAN side and indoor coil is corroded. Tech confirmed indoor coil refrigerant leak near center of U bends on door side of AHU. See video. Confirmed blower and outdoor fan operation. Confirmed zone dampers respond correctly. Bypass counterweight needs to be adjusted. Bypass is fully closed all the time. Due to age and cost of non warranty repairs, tech recommends split system replacement. Need to check on coil replacement cost. See model/serial of AHU. Caleb scheduled for tomorrow.