Job Checkin

Upon arrival tech began performing full CMA Service on 6 split systems, 3 mini splits, 1 dehumidifier and 1 rooftop make up air system. AHU #5 blower motor is rated for 6amps and is drawing 6.29amps, tech recommends replacing motor before it fails. CU #4 Compressor Capacitor is rated for 70mfd and reading 64.97 which is just below spec range and will need to be replaced to avoid potential down time. CU #2 OD Fan capacitor is rated for 5mfd and reading 3.54mfd which is well below spec range and recommends replacing. All other systems are operational with no further challenges. Tech emailed estimates for all 3 findings to email on file. Systems are operational at this time.