-Performed CMA Full Service on 6 Split System Heat Pumps and 1 Mini Split Heat Pump. -Mini Split System - 2006 LG 0.5 Ton Split Heat Pump: Elevator Room: No air filters in place, as previously reported. -System 1 - 2023 Goodman 4 Ton Split Heat Pump 7428: 3rd Floor: Damage to drain line between floors, as previously reported. Maintenance has been unable to find contractor to repair damaged pipe since renovations. Maintenance is currently draining condensation into tub and emptying tub as needed. Condensation pump was recommended for replacement prior due to non operation due to physical damage, but would not correct current drainage issue. -System 3 - 2022 Bryant/Carrier 5 Ton Split Heat Pump 4165: Kitchen/Dining: System has been previously recommended for addition of an EZ Trap to condensate drain line to allow proper cleaning & servicing of drain line/trap. Difficult access; additional time and materials needed. Provided updated estimate. -System 4 - 2010 York/Nordyne 2 Ton R22 S