PERFORMED CMA INSPECTION ON 3 UV LIGHTS, 3 SPLIT SYSTEMS AND 3 GAS FURNACE SYSTEMS. SPLIT SYSTEM #2 , AIR HANDLER #2 AUXILIARY DRAIN PAN WAS FULL UPON ARRIVAL, TECH USED SHOP VACUUM TO GET ALL WATER AND CONDENSATION OUT OF DRAIN PAN , TECH FLUSHED DRAIN LINES OUT TO ENSURE PROPER DRAINAGE. SPLIT SYSTEM #2 COMPRESSER MEGGED IN THE CAUTION, SIGN THAT COMPRESSER IS GOING BAD, RECOMMEND REPLACING SYSTEM IN THE NEAR FUTURE. TECH SPOKE WITH STORE MANAGEMENT AND THEY WOULD LIKE SOME QUOTES FOR REPLACING SPLIT SYSTEM #2. AIR HANDLER #3 BLOWER MOTOR BELT (A47) HAS NICKS AND CUTS IN BELT, BELT IS DUE FOR FAILURE, RECOMMEND REPLACEMENT OF BLOWER BELT, THERE IS AN ESTIMATE PROVIDED FOR REPLACEMENT OF BLOWER BELT. TECH WAS GIVEN APPROVAL TO REPLACE A47 BLOWER MOTOR BELT FOR SPLIT SYSTEM #3. TECH COMFIRMED ALL UV LIGHTS ARE FUNCTIONING PROPERLY AND TECH COMPLETED FILTER CHANGE OF 9-16x25x1 FILTERS. THERE ARE PICTURES AND A PERFORMANCE REPORT ATTACHED TO THIS INVOICE.