-Performed CMA Full Service on 9 Split System Heat Pumps and 1 Dehumidifier. -Office Building System: Compressor side of dual run capacitor tested very weak. No room to add additional capacitor, recommend replacement of dual run capacitor. System is over 20 yr old R22 refrigerant. Customer should consider replacing system. -Building H: Dehumidifier run into existing drain line. Vent on wrong side of trap. Recommend adding EZ Trap to properly vent and service drain line. -Building J: Blower motor capacitor tested weak. Recommend replacement of capacitor. Outdoor fan motor hot to the touch. Compressor megged as caution. Windings deteriorating and due for shorting/failure. Signs of heat damage at condenser unit wiring. Temperature difference in cooling not as expected. Air handler approximately 20 yr old. Condenser approximately 30 yr old. R22. Replacement of system is recommended. -Building L: Compresso