Upon arrival tech was informed thermostat had gone blank from storm. Inspected system and found a burnt wire going from the compressor contactor to the capacitor and the 3amp low voltage fuse blown. Installed resettable fuse and found the thermostat was shorted cause fuse to blow. Tech repaired damaged wire replaced 3amp fuse and installed Focus Pro 5000 thermostat with backplate. Turned power back on and system began heating. Temps and amp draws are within range. System is back operational at this time.