Upon arrival tech found system in the off position, tech then ran system from thermostat and found blower not running and then made a “pop” noise. Tech took out blower and made sure no live wires were touching and made the conclusion that blower motor had failed. Tech explained to homeowner blower motor had been probably running poorly before capacitor change out causing motor to over amp and windings to go out. Tech could not see or locate data tag on blower to get the correct rpm’s and horse power. Office will need to look up what type of motor will need to be replaced. Homeowner stated to just leave blower motor out for right now. No charge for tonight’s visit due to recent repair/premium customer. System is currently down at the moment until we replace blower motor.