David  S.

David S. Job Checkin

-Performed CMA Full Service on 7 geothermal systems. -System 1: Lobby & Reception: Compressor capacitor tested weak. Recommend replacement of capacitor. Provided estimate $226.59. -System 2: Front of Left Hallway: Compressor capacitor tested weak. Recommend replacement of capacitor. Provided estimate $226.59. -System 4: Back side of filter access not secured upon arrival due to improper filter sizes. Corrected and secured as appropriate. -System 6: Left Side of Central Hallway: Primary drain pan appears to be leaking into auxiliary pan (See picture on related form). Found unsecured connection of drain pipe to primary drain pan. Temporary repairs have been attempted prior; unsuccessfully. Reconnected pipe and sealed with pvc glue & silicone as able. Back side of filter access not secured upon arrival due to improper filter sizes. Corrected and secured as appropriate. -System 7: Right Side of Central Hallway: Administrator states thermostat not satisfying at set cooling temperatur


Spencer C.

Spencer C. Job Checkin

Customer stated that water was entering the ceiling after rain. They had a roofing company inspect the roof and found entering RTU 2 and flowing down the curb. Tech found drain clear and draining properly. In the pictures shown by the manager, water was coming from the roof and was not entering through the return duct. Tech found unit insulation had been siliconed and found all insulation intact. Tech did find screws missing from the cabinet and installed new screws. Recommended a second opinion from a different roofing company to see if they saw the same issue


Open  T.

Open T. Job Checkin

Performed Cma inspection on 5 rooftop gas package systems. All systems cooling properly at this time. Contact (Dean) stated System 2 leaks when raining. Requests resealing of unit/rooftop. Did not observe any cause for leaking. Maintenance tech not equipped to search in depth for cause of leak. Added silicone sealant to top seal on unit access doors. System should be monitored for leaking at next rainfall. Unit may be in need of in depth leak search.


Percy M.

Percy M. Job Checkin

Resolution unit serial# 5611D01610 tech service and check. Clean coils clean blower blower motor amps 3.60 compressor#1 amps 4.60 compressor#2 amps 4.66 compressor#3 amps 5.80 fan#1 motor amps 2.11 fan#2 motor amps 2.15 fan#3 motor amps 2.20 fan#4 motor amps 2.00 burners good capacitors good change air filters. Unit operating correctly at this time. Resolution unit serial# 5611D01365 tech service and check system. Coils clean blower clean compressor amps 6.90 fan motor amps 1.67 blower motor 1.56 capacitor good clean drain line change filters. Unit operating correctly at this time. Resolution unit serial# 5611D01608 tech service and check system. Clean coils clean blower blower motor amps 3.54 compressor#1 amps 4.00 compressor#2 amps 4.50 compressor#3 amps 4.77 fan#1 motor amps 1.32 fan#2 motor amps 1.11 fan#3 motor amps 1.45 capacitor good change air filters. Unit operating correctly at this time. Resolution unit serial# 5611D01366 tech service and check system. Clean coils clean blow


Randy K.

Randy K. Job Checkin

Filter change on 5 Lennox gas package units.