2330 Indian Springs Rd
Dudley, NC 28333
(919) 734-9611

Our Top Cities


Job Locations
for sanford, nc


Map of Sanford NC
David  S.

David S.


Job Checkin

-Performed CMA Full Service on 7 geothermal systems. -System 1: Lobby & Reception: Compressor capacitor tested weak. Recommend replacement of capacitor. Provided estimate $226.59. -System 2: Front of Left Hallway: Compressor capacitor tested weak. Recommend replacement of capacitor. Provided estimate $226.59. -System 4: Back side of filter access not secured upon arrival due to improper filter sizes. Corrected and secured as appropriate. -System 6: Left Side of Central Hallway: Primary drain pan appears to be leaking into auxiliary pan (See picture on related form). Found unsecured connection of drain pipe to primary drain pan. Temporary repairs have been attempted prior; unsuccessfully. Reconnected pipe and sealed with pvc glue & silicone as able. Back side of filter access not secured upon arrival due to improper filter sizes. Corrected and secured as appropriate. -System 7: Right Side of Central Hallway: Administrator states thermostat not satisfying at set cooling temperatur