Found alert code on the VFD board indicating a “broken belt alarm”. Belt is good and tension as well. Went spoke with our install supervisor about the findings and ended up increasing the tolerance level of the “broken belt” parameter 22-61. Factory setting is 10%. Tech tested the system afterwards in cooling and waited for it to reach set temperature at the thermostat. Indoor blower torque range stayed between 130-140% operating at full speed. System was tested from the thermostats from “off” to “cool” multiple times and system started up without challenges. Covered under install warranty. Split system for the break room is still down for now. Thermostat temp went from 75 to 73 degrees during cooling.