2308 Indian Springs Rd
Dudley, NC 28333
(919) 734-9611

Our Top Cities


Job Locations
for shallotte, nc


Map of Shallotte NC
Matthew L.

Matthew L.


Job Checkin

Upon arrival tech found system with a compressor contractor fault dated for 5/28, the day before last visit. The thermostat was found to be blank, tech found the auxiliary drain pan full and pan switch tripped. Tech removed water from auxiliary pan and cleared fault. System cycled came on and ran with no challenges. Tech installed drain on the auxiliary pan and ran outside the building. Tech collected operating information of system. Tech only seen a few drops of water from air cabinet when unit was cycled off. Tech did find some insulation curled up in corner near drain of air handler. There was some water droplets on the filters, tech lowered blower capacity from 75% to 70% to decrease coil temperature, to help condensation adhere to coil.