{1968 Carrier Packaged Heat Pump - Chapel} — Tech found metal cap designed to shield the condenser fan motor from rain was insecure and making contact with fan blades during operation. — Noted motor lubricant accumulating on the underside of the motor and noted that the motor is open-winding on both ends. Motor shaft is not firmly seated and has a lot of play. Recommended replacing fan motor with correct model; customer opted not to replace at this time. — Customer authorized tech to re-secure rain shield to condenser fan motor and expressed interest in running the system until a major repair is needed. Customer acknowledged equipment age and condition and that this repair is not a permanent solution. System is operating normally at this time. Emailed bill.