2330 Indian Springs Rd
Dudley, NC 28333
(919) 734-9611

Our Top Cities


Local Reviews
for trenton, nc

Rated 4.9 out of 5 stars based on 7 customer reviews

Excellent, very professional and knowledgeable

I love Jackson & Son”s. They have been nothing but a blessing to me and my kids. Everyone is so nice and professional. They have truly been great to me. I wish each and every employee nothing but the best. They have improved my quality of life and I’m thankful.

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Excellent

He was prompt. Listened to my issues and he was so professional that he knew how to solve the problem. His knowledge and experience truly showed. Great guy. Great company #1

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Excellent

He was prompt and on time. Very professional and courteous. Very helpful and friendly.

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Great service!

Kenny was polite and professional.

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Randy is top notch

Love working with Randy. He’s knowledgeable, quick, and really easy to talk to

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Great Service; Very Positive Attitude

Matt was thorough; explained the repair and was very professional.

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Great Service

  • Overall Experience
  • Quality
  • Experience
  • Punctuality

Job Locations
for trenton, nc

Joseph C.

Joseph C. Job Checkin

Tech arrived and found system and thermostat operating properly, tech pulled t stat off wall and found lots of moisture in thermostat. Tech found hot humid air coming in from hole behind t stat, tech sealed with foam insulation and sealant. No further challenges at this time


Derek J.

Derek J. Job Checkin

Upon arrival tech sealed hood from where underpinning was installed. Tech also replaced FP5000 with new VP8000 and wired for second stage. System is back operational at this time.


Spencer C.

Spencer C. Job Checkin

Tech found system operating properly but customer stated thermostat just came back on and was showing an error before. Based on previous techs notes, tech suspects thermostat issue. Tech also found bugs in thermostat. Tech replaced thermostat and verified system is operating properly. Contactor warranty.


Joseph C.

Joseph C. Job Checkin

Tech found system cooling properly upon arrival, tech noticed high humidity and found the fan was in the on position tech put back to auto system dropped 2 degrees while tech was on site. Customer explained issues with thermostat and it sounds like it had a t stat sensor error.


Kyle W.

Kyle W. Job Checkin

SYSTEM SET ON 60 UPON ARRIVAL. FOUND COMPRESSOR DRAWING PEAK OF AMP DRAW RATING, AND SYSTEM RUNNING HIGH HEAD PRESSURE DUE TO EXTREMELY CLOGGED CONDENSER COILS. FILTER COMPLETELY CLOGGED AS WELL. INVESTED IN PSA (1) SYSTEM. PERFORMED 1ST VISIT PER OFFICE. AMP DRAWS/PRESSURE BACK TO SPECS. SYSTEM IS 22 YEARS OLD AND MAJORITY OF CRAWLSPACE INSULATION HAS FALLEN, EXPOSING METAL DUCTS. CANNOT GUARANTEE SYSTEM PERFORMANCE ESPECIALLY ON HOT DAYS. SET TO 69 PER REQUEST.


David  S.

David S. Job Checkin

-Performed CMA Inspection on 1 Trane Split AC System and 1 Marvair wall Mount AC System. -Found no challenges with systems. Operating correctly at this time. Filter count/size should be updated per equipment list.


Wayne  T.

Wayne T. Job Checkin

4 TON GOODMAN SPLIT SYTEM HEAT PUMP


Kenny C.

Kenny C. Job Checkin

Performed ESA, no issues at todays visit. Landscaping around system is in very poor condition. Poison ivy was located all around unit. Could not access certain parts of the system due to shrubs and poison ivy. Tech serviced unit the best as possible. Renewal to be billed out.


Matthew L.

Matthew L. Job Checkin

Tech found split system condenser not running due to a failed 35/5uf dual run capacitor. Customer approved housecall and capacitor. Renewed agreement on 2 system MSA. Put card on file. Next visit in 6 months. System is back cooling. Put warranty label on capacitor.


Kyle W.

Kyle W. Job Checkin

FOUND EVAPORATOR COIL DRIPPING INTO RETURN PLENUM DUE TO LOW R22 CHARGE/HEAVY CORROSION. SYSTEM IS 35 YEARS OLD EVAPORATOR COIL IS UNAVAILABLE FOR REPLACEMENT. HANDED OVER TO FIELD SUPERVISOR. UNABLE TO CONTACT TIM. MANAGEMENT REFERRED MRS. PRESLEY, WHO PAID FOR TODAYS VISIT VIA PHONE. PRESLEY- (704)-986-7242 CALL WITH PROPOSAL.


Kyle W.

Kyle W. Job Checkin

22 YEAR OLD R22 SYSTEM. FOUND OUTDOOR FAN MOTOR BEARINGS FAILING CAUSING HIGH AMP DRAW. DUAL RUN CAPACITOR WEAK. BLOWER CAPACITOR LEAKING OIL. COMPRESSOR WINDINGS IN CAUTION RANGE/OVER AMPING. EVAPORATOR COILS HEAVILY RUSTED. HANDED OVER TO FIELD SUPERVISOR.


Kyle W.

Kyle W. Job Checkin

RECOVERED REMAINING REFRIGERANT, REPAIRED LEAK AT DISCHARGE LINE, AND REPLACED FILTER DRIER. PASSED BOTH PRESSURE/VACUUM TESTS. ADDED FACTORY CHARGE OF 12LBS R410A. CYCLED IN HEATING/COOLING. PRESSURES WELL WITHIN SPECS. NO LEAK PRESENT AT TXV LINE. MOVED LINE AWAY FROM DISCHARGE TO PREVENT FURTHER RUBBING AND TAPED. WARRANTY.


Kyle W.

Kyle W. Job Checkin

FOUND SYSTEM ALMOST VOID OF REFRIGERANT UPON ARRIVAL. LOCATED OBVIOUS LEAK WHERE INDOOR TXV DISTRIBUTOR LINE ENTERS SUCTION LINE DUE TO VIBRATION RUBBING THROUGH. NEED TO ORDER AND REPLACE INDOOR TXV ASSEMBLY. CHARGED SYSTEM WITH 11LBS OF R410A FOR TIME BEING PER OFFICE. SYSTEM COOLING/HEATING AT THIS TIME. INVESTED IN ESA (1) SYSTEM.


Matt C.

Matt C. Job Checkin

Tech washed and seen unit Customer will call in and renew


Romario  T.

Romario T. Job Checkin

System #2 was not frozen upon arrival, based on CMA inspection, a modular variable speed indoor blower motor was found not operating correctly. Tech verified the operation of then blower motor and confirmed a faulty/failed indoor blower motor. Not having indoor airflow will cause the system to freeze. Tech provided an estimate for replacement as costumer requested and will like to wait on the repairs for now. System #2 is down for now.