Job Checkin

Upon arrival tech was informed that system would freeze in heat mode, outdoor fan would not run consistently and heat strips might be burnt out. Inspected system and found the condenser fan motor failed. The heat strips had the breakers inside system turned off, turned breakers on and heat strips started working. Tech also suspects restriction in outdoor metering device due to it freezing during heat mode but not cooling. Tech contacted office to have field supervisor come out due to extensive repairs and age of system and performed handoff. System does have heat strip heat.