Performed ESA, tech found no issues at todays visit. Tech cleaned and serviced system. Homeowner invest in media filter, check on filter the next visit.
Tech washed and serviced unit and found no challenges at this time. Customer left during maintenance tech was unable to collect temps.
Tech serviced and cleaned unit per service agreement, tech found no challenges at this time, system is back up and running with a delta t of 20 degrees, system is operating properly at this time.
Upon arrival tech found system not running due to failed limit switch. Tech bypassed switch for testing purposes and system came on properly. Quoted $247.98 to replace switch. Customer is going to call home warranty company. Tech left system as is. No house call per premium agreement.
UPON ARRIVAL TECH NOTICED OUTSIDE CONDENSER FOR SPLIT SYSTEM (CB5F) IS SHORT CYCLING. VIDEO ATTACHED. TECH PERFORMED CMA FULL SERVICE ON 1 MINI SPLIT SYSTEM AND 1 SPLIT SYSTEM , BOTH SYSTEMS ARE PERFORMING PROPERLY, SPLIT SYSTEM SHORT CYCLING MAY BE DUE TO CONTROLS EVERYTHING ON SYSTEM CHECKS OUT.
Performed routine maintenance per energy savings agreement. Upon arriving the technician was met by a Mr. Reid. Technician asked if and. Johnson was here and the gentleman explained that Ms Johnson had passed away around a year ago and had left the house to them. Technician complete routine maintenance and did not find any challenges. The system is heating properly and all electrical is testing to spec. After speaking with the office. The tech was able to confirm that the home is in the hands of Ms Johnson’ daughter Lisa. Tech spoke with Lisa and confirmed she wants to move forward PSA with renewal and pay in a Bi-Annual Plan. Customer did not have the 174.50 plus tax so the tech set her up with the monthly to start out with and when she has the funds available, she can call in to pay the remaining amount.
Performed ESA, homeowner expressed unit would not come on. After further inspection tech found no issues with system. Tech explained unit has a 5min delay when system gets a call. Pressure switches are testing within spec. No issues. Tech cleaned and serviced unit.
-Performed CMA full service on one split system and one rooftop package system. -Split system had previous diagnosis provided for heat not working 10/18/23. System does not operate properly in heat mode. Thermostat currently set to 50 degrees. Observed severe buildup of debris on auxiliary heat strips. Heat strips should be removed and cleaned to safely operate. Actual time and material to be billed upon approval. Recommend installation of EZ Trap to properly service air handler drain lines. Provided estimate $138.80. Outdoor fan capacitor tested weak. Recommend replacement of capacitor. Provided estimate $198.14. -Ceiling grid near air handler poorly supported and damaged prior to service.
-Performed CMA full service on one split system and one mini split system. -Recommend addition of auxiliary drain pan at air handler to protect against flooding area with sensitive equipment. Approximate size 24x24”. Office to provide estimate upon request. -Systems operating correctly at this time.
Tech performed CMA inspection on two systems. Tech adjusted belt tension on Trane package unit, also wrapped wiring in compressor compartment to prevent any potential shorts in the future. Tech found no challenges with this system. Amp draws and capacitors tested within spec. System is heating and cooling properly. Tech inspected Trane split system and found system running fine in cool mode with proper refrigerant pressures. However, once switching to heat mode the system cuts out on high head pressure. Suction pressure is within spec but head pressure gradually rises above 500 until pressure switch opens. Airflow is good, tech found a 6 degree temp difference across filter drier. Drier is restricted, indoor and outdoor TXV are operating properly. Recommend replacing filter drier. Amp draws are within spec, Condensor fan motor is almost over amping. 5MFD run cap for fan motor is testing weak, recommend replacing. Compressor run cap (70MFD) is testing within range. Trane split system is