Tech preformed CMA INSPECTION on 8 Split Systems. Upon inspection tech found Split System #1:Auxiliary pan full of water due to primary drain pan backing up with condensation coming off of coil. Tech found drain line was clogged causing water to not flow properly. With further inspection tech found drain trap was not sufficiently sloped which caused sediment from drain pan to stay in drain trap and clogg drain line. Tech was approved to install EZ Trap. Also tech found Condenser #1 was operating, but had a weak fan capacitor. Tech recommends replacing capacitor and has attached estimate to invoice for cost of repair. Upon inspection of Split System #6 tech found Run capacitor had failed. Tech was approved to replace capacitor. System is up and operating at this time. Tech found Split System #7 was operating but had weak fan capacitor. Tech recommends replacing capacitor. Tech also found Split System #4 operating, system had weak blower capacitor, tech also recommends replacing capacito