Customer stated that AC was not cooling properly. Found condenser fan not operating during cooling cycle. Diagnosed bad capacitor with no meter reading. Replaced capacitor, tested condenser motor windings, cleaned condenser coil as a courtesy. Cycled system in cooling. Checked refrigerant charge, superheat and delta-T. Recommended consideration for unit replacement due to the age of the system. Everything is otherwise operating normally at this time.