Checked operation of the Bryant High efficiency gas furnace. Found unit has water pooling in flu pipe from losing proper pitch during installation of the new evaporator coil. Adjusted pitch Checked rest of operation thoroughly. Static pressures .56, temperature rise 70° increased blower speed, gas pressures 3.52, verified proper CFM 1350. Found flu pipe to be the only issue. Everything is working at this time.