Installing a new ignitor to replace your current one that has failed and testing system for proper operation. Note: Replaced igniter found that burners would not ignite. Burner conditions are poor. Gas pressures were good. Unit is a garage heater that is connected to standing propane tanks with a rubber hose. Manually lit burners with lighter found the blower would not kick on. At one point the burner compartment area caught fire. Checked for vacuum on inducer motor which showed a reading of 1.1. Draft van was also not exhausting properly. Customer did not wish for me to continue a diagnosis. I terminated gas supply and shut gas valve off. Advised customer not to run furnace due to safety reasons as the heat exchanger exhibited signs of being clogged. Recommended replacing system. Photos/Videos have been uploaded and payment for igniter was collected.