Found air filter to be getting restricted. Removed air filter to test system. Found volume dampers to be mostly closed on one run and 2 other dampers half closed. Opened up all volume dampers. Found condenser coil to be very restricted causing poor airflow through condenser. Cleaned condenser coil. Found system low on refrigerant, recharged system. Recommend keeping air filter clean and condensing unit coil clean.