. Inspected indoor unit. Filter is a little dirty. The coil is clean. No leaks on the coil. Blower is clean. The indoor is clean. Went to outdoor unit. Found. The compressor not running. Found the wire for the capacitor broke at the connection. Put new wire connection on. Started system. Compressor came on. It is amping in range. The system is now working properly at this time. Cleaned condenser coil.