Upon arrival tested system, blower is dirty, coil is clean, no leaks. Drain line is clear but has adhesive around the drain pan where it meets the drain line. Turned ac on, blower came on, amped at 1.4amps. Compressor amped at 4.5amps. Outdoor fan amped at 1.3amps. Refrigerant levels are sealed in system but it has a 15° split at this time. System is working properly. Turned power off to system and disconnected system completely. Put system outside and covered it with a tarp. Need 1, 12inch 90° for the return when we come back. Spoke to customer on the phone when I first arrived and explained I would call with a price and she told me just to get it done she was not worried about that. Quoted 8hours(4 today, 4 to reset unit). Pull unit and re install unit, need 12 inch 90. Customer is selling home, will need extra help putting unit back