. Upon arrival turned the system to ac. Went to indoor unit. The 10uf capacitor was very rusted. Showed the customer. The blower is clean. The blower motor amped within the manufacture specifications. The coil is clean. The coil is a little rusted but no leaks at this time. Inspected low and high voltage wiring. All wiring is good and tight. The drain is clear. Went to outdoor unit. The 40/5 capacitor was weak. Quoted to replace it and the 10uf. Customer approved. Installed new 40/5 and 10. Started system. The compressor amped at 6.01. The condenser fan motor amped at .64. Both are within the range per manufacture specifications. The Refrigerant pressures were 65/175. 10 Subcooling. No signs of leaks. The system is now working properly. Signed the customer up for membership.