Arrived at customers residence and was greeted by the customer and was led to the thermostat end it is functioning properly at this time. Customer led me to basement where furnace coil is located began to leak search evaporator coil and And no true evidence of coil leaking at this time. After Leak searching, proceeded to look at outdoor unit and found that system had been overcharged With refrigerant for 410 a refrigerant approximately 2 pounds overcharged. Also found 45 over five capacitor, extremely weak at this time. Also Due to overcharge pressures were extremely high compressor went out on lock Rotor amps. Used customers garden hose to cool down compressor. Remove charge and system is functioning properly at this time. Inform customer that everything is functioning properly at this time. Upon departure thermostat has been set to original customer preference in cool mode. Regular Membership for one system billed monthly.