. Upon arrival customer was stating the coil and some of the duct work was sweating. The evaporator coil is clean. The blower is clean. The blower motor amped at 2.45. The drain is clear and the condensation pump is working properly. Inspected low and high voltage wiring. All wiring is good and tight. Found water in flew pipe and rust holes. Quoted to replace section where the holes are. Went to outdoor unit. The coil was a little dirty. Went ahead and cleaned it. The capacitor checked out at 45/5. The compressor amped at 6.12. The condenser fan motor amped at .52. Both are within the range per manufacture specifications. The Refrigerant pressures were a little low at 99/290. 2 degrees of Subcooling. Quoted to add refrigerant and the customer approved. Added 1 pound and 14 ounces. The Refrigerant pressures were 136/360. 11 degrees of Subcooling. The system is now working properly. Signed customer up for membership. Thomason is the correct last name.