Upon arrival filter for main unit is clean. Went into attic, coil and blower are clean. Drain is clean. Wires are tight. Heater kit came on and shut off properly. Unit is level. Blower amped at 1.1amps. Spoke to customer about taping up some duct work and she approved repairs. Once done, ran downstairs, mini split head is clean, and level. Wires are tight. Both systems on, went outside. Coils are clean. Main unit. Wires tight. Contacter and capacitor checked within specs. Fan amped at 1.1amps. Compressor amped at 5.83amps. Refrigerant Levels where 153/415. It is 78° so it does not show on the chart. System is set to every 30 mins of defrost. Mini split, wires all tight. Refrigerant pressures are within specs. Both disconnect wires are tight. Systems are working good and customer is happy at this time of service.