Cameron S.

Cameron S.


Job Checkin

. Upon arrival spoke with the customer. She showed me the thermostat and the indoor unit. Set the thermostat to heat. Went to indoor unit. Inspected evaporator coil. The coil is clean at this time. Leak searched the indoor coil and didn’t find any leaks at this time. Inspected the blower housing and motor. The blower housing is clean and free of debris. The blower motor amped at 1.52. This is in range per manufacture specifications. The electric heat strips amped at 20.71 and 20.79. Both are within the range per manufacture specifications. Inspected low and high voltage wiring. All wiring is good and tight. The drain clear. The drain safeties are good and working properly. All visible duct work is good and tight. Went to the outdoor unit. The Refrigerant pressures were 112/354. This is within the range per manufacture specifications for the temp. 70 indoor and 50 outdoor. The compressor amped at 5.91. The condenser fan motor amped at .61. Both are within the range per manufacture spe