Upon arrival spoke with the customer. She has had no issues. Filters are clean. Started with main system. Turned stat up, each room is getting good air flow. Went to attic, attic was just spray foamed insulated. Coil and blower are clean. Wires are all tight. No leaks in coil. Cleaned drain line. Unit is level. Board is all correct for cool cloud. Customer had all juice insolation taken out and the flex lines are very “roller coaster”. Took pictures and showed customer and she wanted some options on this and replacement of the trunk line. Went outside, coil is clean. Contacter and capacitor checked within manufacture specs. Fan amped at 1.1amps. Compressor amped at 5.38amps. Refrigerant levels where 101/357. Let system run awhile. Disconnect wires all tight and surge protector is working well. Main unit passes my inspection. Mini split. Coil is clean, filters are clear and wires all tight. Spoke with customer about how she uses it and she is going to try a new mode. Went outside, wire