Job Checkin

arrived to customers residence and was greeted by customer and was led to thermostat. Thermostat is functioning properly at this time. Put refrigerant gages on system on outside unit and has suction pressure of five psi and liquid pressure of 50 at this time. inspect 45/5 Capacitor and is within range this time reading 44.8/5.2 At this time. Inspector condenser oil has little lights dust at this time. Inspected fan motor and blade and they are functioning properly at this time. Fan motor has a drawl of .7 A at this time. Inspected fan motor seals found no evidence of oil leaks from bearings at this time. Refrigerant lines are tight and neat and arm flex. Insulation is intact without any visible defects at this time. Inspected out outside disconnect Square D box with breaker. It is functioning properly at this time. > inspected single pole contactor and it has 246.3 V coming in and out at this time and is functioning properly at this time. Outdoor unit is sitting level on bracket tha