Greeted customer at front door and informed her on what I am doing today for the maintenance. She showed me the location of the units and thermostats. Preformed maintenance inspection on heat pump system. Checked indoor coil and found it to be clean. Preformed leak search on coil and didn't find any leaks at this time. Wiped down blower motor wheel per contract. Checked blower motor capacitor and found it to meet manufacturer set points. Checked blower motor amp draw and found it to meet manufacturer set points. Checked outdoor coil and found it to be clean with no signs of leaks at this time. Checked outdoor capacitor and found it to meet manufacturer set points. Checked compressor and outdoor fan motor amp draws and found them to meet manufacturer set points. Checked pressures with gauges and found them to meet manufacturer set points with current outdoor temperature. Preformed maintenance inspection on heat pump system. Checked indoor coil and found it to be clean. Preformed l