450 Nelms Cir Unit 103
Fredericksburg, VA 22406
(540) 361-6744

Job Locations
for midlothian, va


Map of Midlothian VA
James M.

James M.


Job Checkin

Upon arrival changed filters for customer. Went into attic, changed dampers from winter to summer for customer as asked. Blower and coil are clean. No leaks on coil. Wires are all tight. Heat exchanger checked out good, no cracks. Cleaned drain line. System has pan safety. Indoor unit is level and running good. Went outside, cleaned coil. Contacter and capacitor checked out within specs. Fan amped at .9amps, no signs of oil. Compressor amped at 6.4amps. Refrigerant levels where 115/318, 8° subcool, 70° inside, 64° outside. Priced up comfort options for customer.