Cooling inspection HP AHU Inspected high and low voltage wiring, all electrical wiring is intact and tight at this time. Inspected evaporator coil , coil is clean and free of debris at this time. inspected blower motor, housing and wheel, all is clean and working properly at this time Blower motor is pulling 1.04 amps at this time Delta T is @50.80F at this time Static pressures 0.41 inWC and 0.04 = 0.44 delta P inWC at this time Motor is spinning freely at this time Inspected cabinet for cleanliness, cabinet is clean at this time. Clear drain line, drain is clean at this time. Inspected air filters (1) 20 x 20 x 1 filters is dirty at this time. Customer will purchase and install it . HP Inspected high and low-voltage wiring, all electrical wiring is intact and tight at this time. Inspected 0FM, motor is spinning freely and operating properly at this time. OFM is pulling 0.49 amps at this time. Inspected run capacitor 45/5 -/+6%, capacitor is working within range at this time