Upon arrival checked filters. Spoke with customer and explained what I would be doing today and that I would need to see each vent today. Thermostat is clean, April air stat, and it is level. Turned system on heat to 76°. Went into basement to evaluate the indoor unit. The coil is clean, along with the blower and found no leaks coming from the coil. Wires are all tight. Cleaned ez trap. Heat strips amped within specs. Blower amped at .6amps. Duct is clean and tight. All low voltage wires are tight. 131° air temp coming out of vents, 72° entering. Went outside and evaluated the unit. Coil is clean. Wires low voltage and high are all tight with no burn marks or broken. Contacter is working well, no burn marks. Capacitor is 45/5 and is a 45/5 mfd capacitor. Fan motor amped at 1.1amps and showing no signs of oil leakage at this time. Compressor amped at 5.3amps. Refrigerant levels where found at 128/371. Let system run awhile, and system is working well at this time. System is set fo