Customer showed location of thermostat explained how he would get alerts saying uv light needed to be changed. System has humidifier no uv lights on the system. Initially put system in heat due to home being 67 degrees. Found kink in drain line on humidifier which had tear fixed line. Blower motor is clean amping within manufacturer specifications at this time. Coil is clean free of leaks at this time. When going to the outdoor unit found the coil clean free of debri. Inspected electrical connections on the system which were free of damage. Capacitor was in correct range along with system charge. Customer declined options at this time returned system to normal operation.