I recovered the refrigerant and removed the old coil and EEV. I replaced the coil, EEV and filter drier. I pressurized the system with nitrogen to 400psi for 15 min. No leaks present. I placed the system under vacuum under 300 microns. I charged the system to manufacturer specifications. The system is working properly at this time.