450 Nelms Cir Unit 103
Fredericksburg, VA 22406
(540) 361-6744

Job Locations
for partlow, va


Map of Partlow VA
Jeremy S.

Jeremy S.


Job Checkin

Hallway system. I completed a complimentary refrigerant leak search on the system. I found refrigerant leaks in the evaporator coil. Since this is a major repair. I called and made a manager verification appointment. The compressor meghommed green. The compressor amps are 5.10 in correct range per manufacturer specifications. The condenser fan amps are .50 in correct range per manufacturer specifications. The 45/5 run capacitor is weak. The 1 pole contactor is pitted. The refrigerant pressures are 210/75 in correct range per manufacturer specifications. Laundry room system. I didn’t find any refrigerant leaks on this system. The blower amps are 1.2 in correct range per manufacturer specifications. The compressor amps are 3.34 in correct range per manufacturer specifications. The condenser fan amps are .62 in correct range per manufacturer specifications. The refrigerant pressures are 200/75 in correct range per manufacturer specifications. The 45/5 run capacitor is weak. The 1 p