Arrive at Customers residence and was greeted by customer and led to the thermostat for upstairs unit and it is functioning properly at this time. Inspected 16 x20x1 Filter and it was clean at this time. Found that outdoor unit wasn’t running due to bad 45/5 capacitor and heavily pitted single pole contactor at this time. Replaced capacitor and contactor. System is functioning properly at this time. Fan motor and blade are functioning properly at this time. Fan motor seals are tight and neat without any visible leaks at this time. Electoral connections are tight. Need to the components and wire nut connections are tight and neat without any visible defects or issues at this time. inspected condenser coil and it is clean at this time. Inspected control board outdoor unit and it is functioning properly at this time and without any visible defects or issues at this time. Inspected outdoor disconnect and it is tight and need to side of the home at this time. Refrigerant lines. Are tight a