The ez trap float was triggered not allowing the system to operate. The condensate drain line is clogged. There’s algae buildup in the line and the entrance to the sump pump had a layer of algae across it blocking flow. I vacuumed out the drain line and cleared the entrance. I flushed the drain with a gallon of water to check for any additional blockages. The line is flowing properly at this time. I let the customer know that she can use vinegar in the trap once or twice a month to help prevent fast algae growth. The compressor amps are 5.92 in correct range per manufacturer specifications. The condenser fan amps are .67 in correct range per manufacturer specifications. The refrigerant pressures are 305/115 in correct range per manufacturer specifications. The Contactor and capacitor are in good condition. The system is working properly at this time.