Upon inspection found system overcharged Pressures 315/158 subcooing @21 degrees ( initial readings ) Recovered R410A refrigerant from the system. Pressures and temperatures after recovery 116/231 and 51/68 subcooling @10 degrees at this time Delta T 23F After repairs inspected system . AHU Inspected high and low voltage wiring, all electrical wiring is intact and tight at this time. Inspected evaporator coil , coil is clean and free of debris at this time. inspected and cleaned blower motor, housing and wheel, all is clean and working properly at this time Motor is spinning freely at this time Inspected cabinet for cleanliness, cabinet is clean at this time. Clear drain line, drain is clean at this time. Inspected air filter, air filter is new at this time. HP Inspected high and low-voltage wiring, all electrical wiring is intact and tight at this time. Inspected 0FM, motor is spinning freely and operating properly at this time. Inspected run capacitor, capacitor is working