Performed club rejuvenation cleaning, 16X20X1 media air ranger filter isn't the correct type filter. Checked humidifier Aprilaire 600 series pad is clean. Exhaust removal system factory specs 0.50 amps actual 0.23amps exhaust removal voltage enhancement system factory specs 5uf actual 4.91uf hot surface igniter has 0.51amps clean flame sensor. Air movement has a ECM motor,blower wheel is clean. Found exhaust piping leaking at fitting joint. Needs to be cut out and replaced. Burner tubs has concerns of rust. Heat exchanger has some rust system. System has a heat rise of 52 degrees