Heat rise 16 degrees. Changed air filter. Static pressure .5inWC. coils have no leaks. Cleaned indoor fan. Indoor voltage enhancement system reads 9uf rated for 10uf and is within the allowable fault. Electric backup heat system is working properly. Indoor fan is pulling 1.6 amps. Outdoor voltage enhancement system is rated 40/5uf actual is 40/4.7uf and is within the allowable fault. Found that one of the outdoor refrigeration valve is leaking a lot of refrigerant. Outdoor system is low on charge. Outdoor refrigerant pumping system reads 1000-400 megaohms. Recommend silver repair option to replace both valves.