Furnace rejuvenation. Air circulation system is clean, drawing 7.0 amps. The voltage enhancement system is slightly out of specifications with a reading of 6.73. The combustion exhaust system is working properly, drawing 0.6 amps and it's voltage enhancer is within specifications with a reading of 3.97. Return air is 70 degrees, supply air is 132 degrees, temperature rise is 62 degrees. System static pressure is high, -.41" return, +.55" supply for a total of .96". Cleaned flame sensor. Flame safety system is working properly. Air filter is clean. There is furnace condensate leaking from the flue pipe. There is corrosion on the furnace heat transfer media and on the air conditioner heat transfer media.