No A/C, checked system and found that the outdoor voltage enhancement system had failed, factory spec 40/4, actual 0/0, in addition the outdoor air movement system has failed, both need to be replaced. Installed replacement outdoor air movement system and voltage enhancement system, test ran, compressor run load amps factory spec 12.8, actual 4.5, outdoor fan full load amps factory spec 1.3, actual .9, with 55deg supply air temperature. WO-TNFR140992