Club ac rejuvenation, supply has a temperature of 40 degrees. Return has a temperature of 59 degrees. Delta t of 19 degrees. Blower wheel voltage enhancement system is reading 12.3uf and with a factory spec of 12uf it is within the allowable fault. All indoor board connections are good. Filter is clean. Outdoor voltage enhancement system is reading 39.8/4.9uf and with a factory spec of 40/5uf it is within the allowable fault. The electrical gateway is without any pitting. Cleaned off outdoor coil as well as the bottom of the unit to clear drain holes. Fla of .5. Rla of 5.5. Wd40 wipedown of outdoor unit. System is operating normally at this time.